arjenhiemstra/ithowifi

Losing System status (2401) counters after a while

Opened this issue · 3 comments

Describe the bug

After booting up, All counters work. 2401 and 4210. After a few hours, only the 4210 counters remain.

Working situation at 29-05-2024 14:35

This is from the MQTT server:

{"Outside temp (°C)":20.66,"Boiler temp down (°C)":59.45,"Boiler temp up (°C)":58.92,"Evaporator temp (°C)":16.58,"Suction gas temp (°C)":28.6,"Compressed gas temp (°C)":52.04,"Liquid temp (°C)":42.5,"Temp to source (°C)":15.89,"Temp from source (°C)":17.84,"CV supply temp (°C)":25.16,"CV return temp (°C)":30.5,"CV pressure (Bar)":2.17,"Compressor current (A)":0,"Current e-element (A)":0,"Pressure switch":0,"Tariff":0,"Condensation protection":0,"Spare input":0,"Correction measurement delta source temperature (K)":-0.57,"Flow sensor (lt_hr)":0,"Phase detection":0,"Cv pump (%)":0,"Well pump (%)":0,"Boiler pump (%)":0,"Free cooling valve (%)":100,"CV_DHW or cooling temp valve (%)":0,"Compressor":0,"Element":0,"Trickle heating":0,"Error":1,"Free cooling":1,"Expansion valve (pls)":0,"Room temp (°C)":20.08,"Requested room temp (°C)":20,"Heat demand thermost. (%)":0,"Status":4,"Sub_status":255,"Blockage":0,"Calculated evaporation temp CV (°C)":16.08,"Calculated CV condensation temp (°C)":45.18,"Calculated evaporation temp DHW (°C)":16.08,"Calculated condensation temp DHW (°C)":45.18,"Error_found":0,"Error_retry":0,"Task active":0,"Manual operation":0,"Compr block (sec)":0,"Elek block (sec)":0,"Cv for _ naddraai (sec)":0,"Source for _ nadraai (sec)":0,"Boiler for _ nadraai (sec)":0,"Delay electr (sec)":0,"Min running time compr (sec)":0,"Drain time (sec)":0,"EV pressure offset (sec)":0,"EV adjust (sec)":0,"Free cooling interval (sec)":180,"Manual control (sec)":0,"Low pressure timer (sec)":0,"Compressor start (sec)":0,"Compr power on delay (sec)":0,"Delay cv start (sec)":0,"Delay cv stop (sec)":0,"Adaptive timer (sec)":0,"Adaptive overheat (K)":5.5,"adaptive fifo index":8,"Fault highest priority":0,"UTC time":1,"Max CV return temp (°C)":10,"Source pump speed free cooling mode":0,"Compressor in Cv mode":0,"Compressor in boiler mode":0,"Element in CV mode":0,"Element in boiler mode":0,"CV mode blocked":0,"Boiler mode blocked":0,"Free cooling mode blocked":0,"Bleeding mode blocked":0,"Electr element blocked":0,"Electr element DHW blocked":0,"Compressor blocked":0,"Off mode active":0,"CV mode active":0,"Boiler mode active":0,"Free cooling mode active":1,"CV pump prime":0,"Well pump prime":0,"Element released":0,"Additional cooling release":0,"CV enabled":0,"Free cooling enabled":1,"Tariff low from thermostat":0,"Venting from thermostat":0,"ECO selected on thermostat":0,"Comfort selected on thermostat":1,"Boiler blocked from thermostat":0,"Boiler boost from thermostat":0,"Heat demand total (%)":0,"E-consumption during stand-by (kWh)":0,"E-consumption during heating (kWh)":0,"E-consumption during DHW (kWh)":0,"E-consumption during cooling (kWh)":0,"Preheat tap water":0,"Element blocked during retry":1,"Pi error sourceflow":0,"Current source valve position (%)":0,"Utc Time offset (min)":0,"Free cooling block time (min)":0,"Cooling temp control valve setpoint (%)":0,"CO valve position (%)":0,"HRU blowout temp (°C)":22.66,"HRU blowout flow (m3_h)":150,"Regeneration active":0,"Latest valid source supply temp. (°C)":12.54,"Source pump flow setpoint (l_h)":1600,"Well pump speed at compr (%)":0,"Source pump speed at free cooling (%)":0,"Well pump speed at airreg (%)":0,"Free cooling mode":2,"Time CO valve start position (sec)":0,"Minimum release time external cooling (sec)":0,"Block time-release external cooling (sec)":0,"External heating release time (sec)":0,"Blocking time trickle low after power-up (sec.)":0,"Blocking time trickle low after CV operation (sec)":0,"Block time pre-heating tap water (sec)":0,"Slow start well pump (sec)":0,"Source return temperature too low (sec.)":0,"Source flow control period (sec)":0,"Stabilisation waiting time-free cooling (sec.)":0,"Minimum time for preheating potable water (sec)":0,"Maximum time for preheating potable water (sec)":0,"Electrical element release (min)":0}

Syslog since turning on:

  18442 I: I2C init: QueryStatus
     18256 I: Hostname: nrg-itho-9e4c
     18078 I: mDNS: started
     17664 I: I2C init: QueryStatusFormat - items:134
     17410 I: Webserver: started
     17144 I: MQTT: connected, System config: 1
     16917 I: I2C init: QueryDevicetype - mfr:0x00 type:0x0D fw:0x25 hw:0x4E
     14795 I: Timezone: Europe/Amsterdam, specifier CET-1CEST,M3.5.0,M10.5.0/3 
     14628 I: WiFi: connection successful
      8710 I: wifi AP mode started
      6963 E: Unable to set wifi disconnect
      4524 I: I2C sniffer capable hardware: yes
      4322 I: HW rev: NON-CVE 1, FW ver.: 2.8.0
      3804 I: Device UUID: 993c8f2b-1d34-4771-82fe-35acee3d2f54
      3492 I: System boot, last reset reason: POWERON_RESET

counters
80 82 C2 10 01 35 1A 11 49 12 B2 01 9A 05 B8 00 00 04 80 01 AF 0D 4C 27 1C 0B 33 0B 42 06 51 08 95 00 00 06 1A 02 C2 01 14 00 11 00 00 00 00 00 00 00 00 00 00 00 00 02 C2 02 40 07

Connection:
Config version: 005
Itho I2C connection status: connected
File system: 32768 bytes used / 131072 bytes total

Then, at 29-05-2024 21:12

MQTT

{"CH pump on (h)":4432,"Source pump on (h)":4792,"DHW pump on (h)":410,"Compressor on (h)":1464,"Electrical element on (h)":0,"CH mode (h)":1152,"DHW mode (h)":431,"Free cooling mode (h)":3410,"Total runtime (h)":10018,"CH pump starts":2868,"Source pump starts":2883,"DHW pump starts":1617,"Compressor starts":2197,"Electrical element starts":0,"CH mode starts":1562,"DHW mode starts":706,"Free cooling starts":276,"System starts":17,"DHW element on (h)":0,"DHW element starts":0,"E-consumption stand-by (kWh)":0,"E-consumption heating (kWh)":0,"E-consumption DHW (kWh)":0,"E-consumption cooling (kWh)":0,"Energy out of source (MWh)":706,"Energy returned to source (MWh)":577}

Syslogs since last messages:

2024-05-29 16:48:34 I: I2C init: QueryStatus
2024-05-29 16:48:34 I: I2C init: QueryStatusFormat - items:0
2024-05-29 16:48:34 I: I2C init: QueryDevicetype - mfr:0x00 type:0x0D fw:0x25 hw:0x4E
2024-05-29 16:48:34 I: Hostname: nrg-itho-9e4c
2024-05-29 16:48:33 I: mDNS: started
2024-05-29 16:48:33 I: Webserver: started
2024-05-29 16:48:33 I: MQTT: connected, System config: 1
2024-05-29 16:48:31 I: Timezone: Europe/Amsterdam, specifier CET-1CEST,M3.5.0,M10.5.0/3 
2024-05-29 16:44:49 I: WiFi: connection successful
2024-05-29 16:44:43 I: wifi AP mode started
2024-05-29 16:44:41 E: Unable to set wifi disconnect
2024-05-29 16:44:38 I: I2C sniffer capable hardware: yes
2024-05-29 16:44:38 I: HW rev: NON-CVE 1, FW ver.: 2.8.0
2024-05-29 16:44:38 I: Device UUID: 993c8f2b-1d34-4771-82fe-35acee3d2f54
2024-05-29 16:44:37 I: System boot, last reset reason: OWDT_RESET
2024-05-29 16:44:33 E: Unable to set wifi disconnect
2024-05-29 16:44:30 I: I2C sniffer capable hardware: yes
2024-05-29 16:44:30 I: HW rev: NON-CVE 1, FW ver.: 2.8.0
2024-05-29 16:44:30 I: Device UUID: 993c8f2b-1d34-4771-82fe-35acee3d2f54
2024-05-29 16:44:30 I: System boot, last reset reason: OWDT_RESET
2024-05-29 16:44:25 E: Unable to set wifi disconnect
2024-05-29 16:44:23 I: I2C sniffer capable hardware: yes
2024-05-29 16:44:22 I: HW rev: NON-CVE 1, FW ver.: 2.8.0
2024-05-29 16:44:22 I: Device UUID: 993c8f2b-1d34-4771-82fe-35acee3d2f54
2024-05-29 16:44:22 I: System boot, last reset reason: SDIO_RESET
2024-05-29 16:47:34 W: Warning: Task MQTT timed out!

counters

80 82 C2 10 01 35 1A 11 50 12 B8 01 9A 05 B8 00 00 04 80 01 AF 0D 52 27 23 0B 34 0B 43 06 51 08 95 00 00 06 1A 02 C2 01 14 00 11 00 00 00 00 00 00 00 00 00 00 00 00 02 C2 02 41 EA

Connection:
Config version: 005
Itho I2C connection status: connected
File system: 32768 bytes used / 131072 bytes total

To Reproduce
Steps to reproduce the behaviour:
unknown

Expected behaviour
All counts stay active.

Screenshots
Screenshot 2024-05-29 at 21 28 31
Import of the MQTT into homeassistant. You can see the counters working until 16:45.

Device information

  • Firmware version 2.8.0
  • Hardware revision non-cve 1.
  • Type/model number Itho (on sticker outside the box) wpu 5g
    hw version: 78
    fw version: 37
  • CC1101 RF module enabled no
  • In case of wifi issues, wifi access point make and model:

Debug logging
Please provide debug logging from the debug page if possible:

See above in description.

What is the output of "Query Status" on the debug page? (FYI; Query Status == 2401 command)

Query status
Result: 80 82 A4 01 01 D5 05 E9 16 5D 16 79 07 06 08 02 09 F8 09 3A 06 7C 05 44 07 08 07 46 01 21 00 00 00 00 00 00 00 00 FF C7 00 F5 00 64 06 00 64 64 00 00 00 01 01 00 00 07 E5 07 D0 00 04 FF 00 06 D4 09 B9 06 D4 09 B9 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 02 26 08 00 66 57 AF 45 0A 06 00 00 00 00 00 00 00 00 00 00 00 00 00 00 01 00 00 00 00 00 01 00 00 00 01 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 01 00 00 00 00 00 00 00 64 00 06 B1 00 96 00 06 7C 06 40 00 06 00 01 00 00 00 00 00 00 00 00 00 00 00 00 00 00 01 00 00 00 00 00 00 00 00 00 00 00 00 00 00 8C

and Query 2410

Result: 80 82 A4 10 01 13 00 00 00 00 00 00 00 00 FF FF FF FF 00 00 00 01 10 00 F0 39
Current: 0
Minimum value: 0
Maximum value: 65535

Just to clarify, the 2401 counters don't show up on the "Itho Status" page ether. MQTT matches what's on the status page.