ioBroker/ioBroker.hm-rpc

State value to set for "hm-rpc.3.INT0000007.1.SET_TEMPERATURE" has value "30.5" greater than max "30"

Bratmaxe1981 opened this issue · 3 comments

It affects the Homematic radiator thermostats HM-CC-RT-DN which can be set in the range of 5°C-30°C.
In addition, there are the valid values
​​ 4.5°C = OFF = valve 0% open
30.5°C = ON = valve 100% open.

Please adjust the value range to 4.5-30, then the error in IOBroker should be fixed!

to reproduce you can set the Actor to ON or OFF in der Webinterface and the message will be set!

Have you tried a force reinit run? afaik, the problem should be fixed. OR maybe it is just very similar.

Thanks for the super fast response.
I restarted the adapter and also had the devices read in completely again.
The 1.15.16 is installed

same Problem

maybe it's because the heating group reports to me and not the actuator itself!
So I created a heating group in the Homematic and this reports the error. Not the single actor!
Can it be because of that?

150d commented

... just wanted to add that I'm seeing the same problem here with adapter version v1.15.18. A reinit-config has not helped here. And yes, I'm also getting the messages about the group, not the device.