Connecting to a topic name
kaptindan opened this issue · 2 comments
kaptindan commented
kyle-github commented
Based on that picture, I think you want to use CIP bridging. The path will probably be something like "1,3,18,192.168.12.2,1,0". I'll break that down.
1,3 - this routes the traffic into the PLC to the backplane ("1") and then to the slot with the other network card, "3".
18,192.268.12.2 - this tell the network card to use port A (18 is A and 19 is B), and then route traffic to IP address 192.168.12.2 where the second PLC is.
1,0 - this tell the second PLC to route traffic to the backplane, "1", and then to slot 0 where the CPU is.
kaptindan commented
Hey Kyle! Thanks so much for the information! I am still a learner. This helped a lot.