does not read the values "Grid Active, Grid Active, Grid Power, Grid Voltage"
Nando1497 opened this issue · 4 comments
Same problem, solved by change yaml to read states from 4553 register instead 4554
-
platform: modbus_controller
modbus_controller_id: smg_inverter
name: "Grid Active"
id: grid_active
address: 4553
register_type: holding
bitmask: 0x200 -
platform: modbus_controller
modbus_controller_id: smg_inverter
name: "On Battery"
address: 4553
register_type: holding
bitmask: 0x100
hi, changing from 4554 to 4553 I read Grid Active and On Battery, but Grid Power not yet
It often happens that the "output Source Priority" and the "charger Source Priority" change
It often happens that the "output Source Priority" and the "charger Source Priority" change
Related: #48
hi, changing from 4554 to 4553 I read Grid Active and On Battery, but Grid Power not yet
Those depend on the PZEM module. @odya Can we implement a fallback to the values reported by the inverter?