hhaim opened this issue · 1 comments
hhaim commented
I hope this is the right forum -- saw this is Tasmota source code
- SDM 630 v2 modbus FW 13.02/2019
- Connected to
PC->USB->RS485 -> (SDM) -> RS485 monitor (Rx only)-> back to PC using IFFT
- Sending either
(readv) 01 04 00 00 00 02 71 CB
(diag) 01 08 00 00 aa 55 5e 94
-
Oscilloscope is connected to the 485 bus and I see valid RS 485 differential signals
-
I see valid RS485 with the monitor on the same bus
-
Tested it with 2400/1/NP, 9600/1/NP, 38400/1/NP
-
120 ohm terminator is attached
Is there a hidden command that configure SDM enable this mode?
both TTL:485 converters work fine with PC but not with SDM
Am I missing somthing?
hhaim commented
It seems as a faulty SDM630. tested another device and it works fine.