the6p4c/Flatpack2

Set default doesn't stick

IonCaza opened this issue · 1 comments

Hey there, I have a flatpack2 (non-HE) 48v/2000.

I'm able to send a login message to 0x05004804 with the serial number successfully. After login, for 5 seconds I see messages come from 05014004 with status.

I'm also able to send messages to 0x05019C00 with data (0x29, 0x15, 0x00, 0xC0, 0x12) and 0x05FF4004 (or 0x05FF4005) with data (0x2C, 0x01, 0xC0, 0x12, 0xC0, 0x12, 0x24, 0x13) to set voltage to 48V. For 5 seconds, the voltage sticks to 48V but it returns to 53.5V after that. I send all messages together, login, set default, and set voltage.

I can't get it to stick to 48V however... any idea why? Thank you for your help.

Will sending to 05009C00 fix it for you ?