siralexbox opened this issue · 7 comments
Great work,
Nothing happens when I change Work Mode, Charger max current, Discharge max and Min capacity.
Also I cant find the Load/Generator register.
Using solax_x1_hybrid_g3_triplepower.yaml on a X1-Hybrid G3 HV-5.0T
Have you enabled remote control on your Inverter? I had to do this when using RS485.
Upss, done, was the remote control option.
Thanks
Bu still cant find the "load/generator" value, is this calculated from the other values?
Or is there a register just for it?
The load / generator is "SolaX Measured Power" register 70.
Isn't register 70 the Feed in Power?
On the solax app there are different values for injected power and home load.
I have the power meter installed, to allow zero injection, is the home load value coming from this meter?
Can you point me to the registers list.
Thanks
As per the comment:
# Negative pulling from Grid, Positive exporting to the Grid
My setup uses a Eastron SDM230-ModBus energy meter.
There is no official register list available from SolaX
Closed due to no comments for over a week.