Measurements

This repository holds electrical measurements.

AC power measurements have been taken with a RIGOL DS1054Z oscilloscope and a differential probe from Testec, the TT-SI 9001.

Warning: Never connect your oscilloscope to AC power with standard probes! Measuring AC power requires differential probes. For standard probes, the reference voltage is connected internally to case ground and connecting it to AC will essentially connect case ground to AC.

Inrush Current

The measurements were measured over a 0.5 Ω shunt resistor.

Shunt measurement

What Inrush Current Duration
MeanWell RS-15-12 power supply 30 A 1 ms
MeanWell RS-100-5 power supply 44 A 2.7 ms
MeanWell MDR-10-24 power supply 35 A 1 ms
MeanWell APV-16-12 28 A 1 ms
Halogen Lamp, 28 W 1.8 A

MeanWell RS power supplies

Designation of the power supplies: RS-wattage-voltage

RS-15-5, RS-15-12, RS-25-5, RS-25-48 all show the same inrush current of around 30 A, charging for 1 ms.

RS-15-12 inrush RS-25-48 inrush

RS-100-5 at 44 A, charging for 2.7 ms.

RS-100-5 inrush

MeanWell MDR series (DIN rail mount)

MDR-10-24: 35 A, charging for 1 ms.

MDR-10-24 inrush

MeanWell APV series

APV-16-12: 28 A, charging for 1 ms.

APV-16-12 inrush

Philips Classic 28 W Halogen Lamp

Single halogen lamp when turning on: 1.8 A

Single 28 W halogen lamp

Single halogen lamp, attached to a phase control dimmer

Dimmer, single bulb

Three halogen lamps, attached to the same dimmer; 3.8 A

Dimmer, 3 bulbs

Halogen lamp warming up and internal resistance rising.

Dimmer, 3 bulbs, warmup

Various measurements

V-TAC LED lamp, GU 10