Generator Data
Opened this issue · 1 comments
Hi, nice work.
Is it possible to add Datas fromn the Generator Port, like L1,2,3 power, current, volatage. I can not find this values
You can add this to the configuration yaml
` - platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${device_type}-Generator Power L1"
id: "${device_type}_generator_power_l1"
register_type: holding
address: 664
unit_of_measurement: "W"
state_class: "measurement"
accuracy_decimals: 1
filters:
- multiply: 0.1
value_type: U_WORD
-
platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${device_type}-Generator Power L2"
id: "${device_type}_generator_power_l2"
register_type: holding
address: 665
unit_of_measurement: "W"
state_class: "measurement"
accuracy_decimals: 1
value_type: U_WORD -
platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${device_type}-generator power l3"
id: "${device_type}_generator_power_l3"
register_type: holding
address: 666
unit_of_measurement: "W"
state_class: "measurement"
accuracy_decimals: 1
value_type: U_WORD -
platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${device_type}-Generator Voltage Phase L1"
id: "${device_type}_generator_voltage_phase_l1"
register_type: holding
address: 661
unit_of_measurement: "V"
state_class: "measurement"
accuracy_decimals: 1
filters:- multiply: 0.1
value_type: U_WORD
- multiply: 0.1
-
platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${device_type}-Generator Voltage Phase L2"
id: "${device_type}_generator_voltage_phase_l2"
register_type: holding
address: 662
unit_of_measurement: "V"
state_class: "measurement"
accuracy_decimals: 1
filters:- multiply: 0.1
value_type: U_WORD
- multiply: 0.1
-
platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${device_type}-Generator Voltage Phase L3"
id: "${device_type}_generator_voltage_phase_l3"
register_type: holding
address: 663
unit_of_measurement: "V"
state_class: "measurement"
accuracy_decimals: 1
filters:- multiply: 0.1
value_type: U_WORD
- multiply: 0.1
-
platform: modbus_controller
modbus_controller_id: ${modbus_controller_id}
name: "${device_type}-Generator Power Total"
id: "${device_type}_generator_power_total"
register_type: holding
address: 667
unit_of_measurement: "W"
state_class: "measurement"
accuracy_decimals: 0
value_type: U_WORD
`