/modbus_exporter

Exporter which retrieves stats from a modbus system and exports them via HTTP for Prometheus consumption.

Primary LanguageGoApache License 2.0Apache-2.0

Modbus exporter

Prometheus exporter which retrieves stats from a modbus tcp system and exports them via HTTP for Prometheus consumption.

Scrape sequence

Reproduce diagram

Go to: https://bramp.github.io/js-sequence-diagrams/

Note right of Prometheus: prometheus.yml \n --- \n target: Modbus-TCP-10.0.0.5 \n sub_target: Modbus-Unit-10 \n module: VendorXY
Prometheus->Exporter: http://xxx.de/modbus?target=10.0.0.5&sub_target=10&module=vendorxy
Note right of Exporter: modbus.yml \n --- \n module: VendorXY \n - temperature_a: 400001 \n - temperature_b: 400002

Exporter->Modbus_TCP_10.0.0.5: tcp://10.0.0.5?unit=10&register=400001
Modbus_TCP_10.0.0.5->Modbus_RTU_10: rtu://_?register=400001
Modbus_RTU_10-->Modbus_TCP_10.0.0.5: value=20
Modbus_TCP_10.0.0.5-->Exporter: value=20

Exporter->Modbus_TCP_10.0.0.5: tcp://10.0.0.5?unit=10&register=400002
Modbus_TCP_10.0.0.5->Modbus_RTU_10: rtu://_?register=400002
Modbus_RTU_10-->Modbus_TCP_10.0.0.5: value=19
Modbus_TCP_10.0.0.5-->Exporter: value=19

Exporter-->Prometheus:temperature_a{module="VendorXY",sub_target="10"} 20 \ntemperature_b{module="VendorXY",sub_target="10"} 19

Building

make build

Getting Started

The modbus exporter needs to be passed target (including port), module and sub_module as parameters by Prometheus, this can be done with relabelling (see prometheus.yml).

Once Prometheus is properly configured, run the exporter via:

./modbus_exporter [flags]

Supported flags:

usage: modbus_exporter [<flags>]


Flags:
  -h, --[no-]help                Show context-sensitive help (also try
                                 --help-long and --help-man).
      --config.file=modbus.yml ...  
                                 Sets the configuration file.
      --[no-]web.systemd-socket  Use systemd socket activation listeners instead
                                 of port listeners (Linux only).
      --web.listen-address=:9602 ...  
                                 Addresses on which to expose metrics and web
                                 interface. Repeatable for multiple addresses.
      --web.config.file=""       [EXPERIMENTAL] Path to configuration file that
                                 can enable TLS or authentication.
      --log.level=info           Only log messages with the given severity or
                                 above. One of: [debug, info, warn, error]
      --log.format=logfmt        Output format of log messages. One of: [logfmt,
                                 json]
      --[no-]version             Show application version.

Visit http://localhost:9602/modbus?target=1.2.3.4:502&module=fake&sub_target=1 where 1.2.3.4:502 is the IP and port number of the modbus IP device to get metrics from, while module and sub_target parameters specify which module and subtarget to use from the config file. If your device doesn't use sub-targets you can usually just set it to 1.

Visit http://localhost:9602/metrics to get the metrics of the exporter itself.

Configuration File

Check out modbus.yml for more details on the configuration file format.

The --config.file parameter can be used multiple times to load more than one file. It also supports glob filename matching, e.g. modbus_*.yml.

Systemd service

You can create a systemd service if you want to run modbus exporter as a service in the background. Start by creating a modbus_exporter system account (example on Debian)

useradd -r modbus_exporter

Place the modbus_exporter binary at /usr/local/bin/modbus_exporter

The following example systemd unit file can be saved to /etc/systemd/system/modbus_exporter.service:

[Unit]
Description=Modbus TCP Prometheus exporter
Requires=network.target
After=network-online.target
Wants=network-online.target

[Service]
User=modbus_exporter
Group=nogroup
ExecStart=/usr/local/bin/modbus_exporter --config.file='/etc/modbus_exporter.yml'
Restart=on-failure
RestartSec=1

[Install]
WantedBy=multi-user.target

Then locate your config file in /etc/modbus_exporter.yml, and run the following commands to make systemd aware of config changes and startup the modbus_exporter

systemctl daemon-reload
systemctl start modbus_exporter

In order to start the service at boot, run the following

systemctl enable modbus_exporter

TODO

  • Rework logging.

  • Revisit bit parsing.

  • Print name, version, ... on exporter startup.

Misc info

ModBus RTU

Support for serial ModBus (RTU) was dropped in git commit d06573828793094fd2bdf3e7c5d072e7a4fd381b. Please send a PR if you need it again. For now, we suggest using a ModBus PLC/bridge/master to bridge from RTU into TCP.

Software provenance

This is forked from https://github.com/lupoDharkael/modbus_exporter which was not maintained any more and did not follow Prometheus best practices. Initially, development happened in https://github.com/mxinden/modbus_exporter which has now been retired in favour of https://github.com/RichiH/modbus_exporter .